Energy Container Storage

Energy Container
Integrated system of batteries, control units and inverters is built into the container, which allows easy transport to the destination. Large capacity and power of up to 500 kW is intended primarily for industrial purposes. It can be used not only as a storage of solar or wind energy, but also as a backup source in the event of a blackout.

Energy Storage 20′ Container

Features
Dimensions:6058×2438×2591 mm
Weight:cca 19 t
Ambient temperature / relative humidity:-15~50°C / 5~95% Rh (no condensation)
Maximum altitude:3000 m (over 3000 m capacity decreases)
Noise emission:< 65 dB
Cooling:industry air condition
Protection:IP54
Protection function:overvoltage, undervoltage, overcharge, overdischarge, overheating, short circuit
Ochrana proti požáru:heptafluoropropane extinguishing system
Grid on/off time:< 10 ms
Switching time:< 10 ms
Maximum efficiency:91%
EMS communication port:RS485, G4, LAN
Accessoriescables, lighting, switches, sockets, etc. in the container
AC parametres for grid and off-grid systems
Maximum apparent power AC:275 kVA
Rated power:250 kW
Rated current (maximum):360 A (396 A)
Rated voltage:400 V
Frequency:50 Hz
Power factor:0.9
THDi:< 5%
THDu:< 3% linear
Off-grid overload capability:110% - 10 min, 120% - 1 min
Connection:3×L + N + PE
Battery specifications
Rated energy capacity:1175.04 kWh
Rated capacity:1800 Ah
Charging cycles:≥ 6000 (0.5C, 25°C)
Rated voltage DC:652.8 V
Battery type:lithium iron phosphate
Compliance with the standards, directives and regulations
IEC62619, IEC62040‑1, RoHS, WEE, UN38.3, UL1973, EN50549‑1, G98, G83, G59, AS4777.2:2015, VDE0126‑1‑1, VDE‑AR‑N4105, CEI 0‑21, IEC62109‑1/‑2, EN61000‑6‑1, EN61000‑6‑2, EN61000‑6‑3

Energy Storage 40′ Container

Features
Dimensions:12192×2438×2591 mm
Weight:cca 39 t
Ambient temperature / relative humidity:-15~50°C / 5~95% Rh (no condensation)
Maximum altitude:3000 m (over 3000 m capacity decreases)
Noise emission:< 65 dB
Cooling:industry air condition
Protection:IP54
Protection function:overvoltage, undervoltage, overcharge, overdischarge, overheating, short circuit
Fire protection:heptafluoropropane extinguishing system
Grid on/off time:< 10 ms
Switching time:< 10 ms
Maximum efficiency:91%
EMS communication port:RS485, G4, LAN
Accessoriescables, lighting, switches, sockets, etc. in the container
AC parametres for grid and off-grid systems
Maximum apparent power AC:550 kVA
Rated power:500 kW
Rated current (maximum):721 A (793 A)
Rated voltage:400 V
Frequency:50 Hz
Power factor:0.9
THDi:< 5%
THDu:< 3% linear
Off-grid overload capability:110% - 10 min, 120% - 1 min
Connection:3×L + N + PE
Battery specifications
Rated energy capacity:2350.08 kWh
Rated capacity:3600 Ah
Charging cycles:≥ 6000 (0.5C, 25°C)
Rated voltage DC:652.8 V
Battery type:lithium iron phosphate
Compliance with the standards, directives and regulations
IEC62619, IEC62040‑1, RoHS, WEE, UN38.3, UL1973, EN50549‑1, G98, G83, G59, AS4777.2:2015, VDE0126‑1‑1, VDE‑AR‑N4105, CEI 0‑21, IEC62109‑1/‑2, EN61000‑6‑1, EN61000‑6‑2, EN61000‑6‑3

 